Project Spotlight: Gig Harbor Septic Tank Riser Installation Inspection

Upfront Septic recently completed a septic system inspection and excavation at a property in Gig Harbor, WA, after the homeowner contacted us to verify root intrusion issues identified by another septic company. The customer wanted a second opinion and a closer look at the system to confirm the reported problems and determine what maintenance and repairs were needed.

Upon arrival, our technicians located a two-compartment septic tank and a separate pump tank in the front yard. The septic tank was approximately 24 inches below grade, while the pump tank was approximately 29 inches below grade. During the inspection, we discovered significant root intrusion around the inlet riser, particularly where the riser connects to the tank and where the lid meets the riser. Additional root intrusion was found around the first-compartment riser. The second compartment was approximately 32 inches below grade and did not have a riser, preventing our team from directly inspecting it. Based on the conditions found in the accessible areas, root intrusion is also suspected in the second compartment.

Our technicians also identified lighter root intrusion around the outlet riser and found that both the first-compartment lid and pump tank lid were damaged and need replacement. No root intrusion was observed in or around the pump tank itself. Because previous service reports indicated the septic tank had not been pumped in approximately 11 years, we recommended pumping the entire system as part of the necessary maintenance.

A drawdown test was also performed to evaluate the system's ability to move wastewater. Measurements were recorded at 78 inches and 80 inches, resulting in an average drawdown rate of approximately 1 inch per minute. Based on this result, drainfield maintenance was recommended.

The recommended work includes resealing the inlet and outlet risers, installing an additional riser, replacing damaged riser lids, completing the necessary excavation, and pumping the septic system and pump chamber. Drainfield maintenance is also recommended to address the system's performance concerns. This project has been identified as requiring additional work, and the More Work To Follow (MWTF) appointment has already been scheduled so the recommended maintenance can move forward.

Project Gallery

Our Recent Projects
Gig Harbor
Gig Harbor·Property Sale Inspections & RSS

Gig Harbor Property Sale Inspections & RSS

A point-of-sale inspection in Gig Harbor on a two-compartment concrete tank sitting four inches below grade with no risers. Baffles and tank structure were sound, and a riser over the open inlet lid was the only work recommended.

North Bend
North Bend·Septic Tank Riser Installation

North Bend Septic Tank Riser Installation

The follow-up work on a North Bend property, carrying out what the sale inspection recommended. Risers over all three tank access ports, the mainline connection resealed with hydraulic cement, and a leveler added to a lateral line to even out flow across the drainfield.

Gig Harbor
Gig Harbor·Septic Treatment

Gig Harbor Septic Treatment & Pumping

A Gig Harbor service where the tank itself was sound but the pump tank was not. About 1,400 gallons pumped and the filter cleaned, a gap with roots where the mainline enters the tank, and floats wired so that the pump ran but the high-level alarm stayed silent.

Gig Harbor
Gig Harbor·Septic System Repair

Gig Harbor Septic System Repair

A Gig Harbor service call where the risers sat about six inches below grade, so both tanks had to be dug out to reach the lids. Both were pumped, the effluent filter cleaned and the first-compartment lid replaced. The alarm could not be found and did not sound when the float was raised.

Gig Harbor
Gig Harbor·Septic System Cleaning

Gig Harbor Septic System Cleaning

A six-year-old Gig Harbor system that had never been pumped, called out for summer sewage odor in the yard. The distribution box lid was found cracked, which may be the source. Solids were broken up with a CrustBuster and about 1,000 gallons pumped; the baffles and the tank itself were sound.

Gig Harbor
Gig Harbor·Emergency Septic Services

Gig Harbor Emergency Septic Services

An emergency call in Gig Harbor after a junction box fell into the pump tank. The tank was flooded, smoke and sparking were seen once the pump was run, and about 1,200 gallons were pumped to reach the lid at the bottom. The electrical was left for a qualified professional.

Gig Harbor
Gig Harbor·Septic Company

Gig Harbor Septic Company

A Gig Harbor tank with no risers and roots at every main access opening, including around the inlet and outlet connections. Solids were broken up with a CrustBuster and about 1,125 gallons pumped, a damaged effluent filter was replaced, and five risers plus two resealed connections are planned.

Gig Harbor
Gig Harbor·Septic Service

Gig Harbor Septic Service

A second opinion on a Gig Harbor system after another company's inspection. Root intrusion was found at the ATU riser, the pump tank conveyance line and the junction box, the UV light was disconnected with a broken casing, and the drain field showed no signs of trouble. Pumping was recommended after about three years.

Gig Harbor
Gig Harbor·Septic Tank Pumping

Gig Harbor Septic Tank Pumping

A Gig Harbor pump-out covering both the septic tank and the pump tank. The pump tank lid was replaced while we were there, and the two-piece riser on the first compartment was found with its adapter not sealed tightly, which is booked in for follow-up work.

Woodinville
Woodinville·Septic Tank Riser Installation

Woodinville Septic Tank Riser Installation

A Woodinville riser installation and reseal. Two 24-inch risers and one 12-inch riser resealed to the tank, the transport line excavated and its connection resealed, and a new 12-inch riser fitted over the LCB, all backfilled at the end.

Spanaway
Spanaway·Septic Tank Riser Installation

Spanaway Septic Tank Riser Installation

One 12-inch and two 24-inch risers fitted to give proper access to the tank. The old concrete around the pump tank riser was cut out, the area cleaned and resealed, and every inside rim sealed with hydraulic cement to keep groundwater and roots out.

Gig Harbor
Gig Harbor·Septic Pumping

Gig Harbor Septic Pumping and Inspection

A Gig Harbor homeowner trying us after being let down by their previous company. Routine pumping plus an O&M inspection: approximately 500 gallons from the trash tank, a gap found where the mainline enters it, and a two-amp fuse that blew again as soon as it was replaced — an electrical fault still to be traced.

Gig Harbor
Gig Harbor·Septic Inspections

Gig Harbor Septic Inspection and Repair

A high-level alarm at a Gig Harbor property with the pump tank flooded. We pumped the pump tank and about 1,125 gallons from the septic tank, and the inspection found a pump that would not activate, an unsealed junction box, root intrusion and lid damage.

Gig Harbor
Gig Harbor·Septic Inspections

Septic Pumping and Inspection in Gig Harbor

Upfront Septic recently completed a septic system inspection and maintenance service for a homeowner in Gig Harbor, WA. The project included a comprehensive inspection of the on-site sewage system to evaluate the condition and performance of the entire system, helping ensure it was operating safely and efficiently. As part of the visit, our technicians pumped […]

Redmond
Redmond·Septic Tank Riser Installation

Septic System Excavation & Riser Installation Project in Redmond, WA

Our team recently completed a septic system excavation and inspection project for a homeowner in Redmond, WA after concerns about root intrusion inside the septic tank. The goal was to expose the tank, inspect its condition, eliminate the source of the root intrusion, and make future maintenance much easier. After arriving on site, we excavated […]

Read More:
How Long Does It Take to Pump a Septic Tank?
How Long Does It Take to Pump a Septic Tank?

Most residential septic pumping appointments take roughly 30 minutes to two hours, but the actual time depends on the tank size, how easy the tank is to reach, its condition, and how much has built up inside it.

Is Charmin Toilet Paper Septic Safe?
Is Charmin Toilet Paper Septic Safe?

Many Charmin products break down with water and suit a well-maintained septic system, but the product, the amount used and the condition of your tank all matter. What to look for, why flushable wipes are a different question, and when the paper is not the real problem.

Records Show 1 in 10 King County Food Vendors Had a Plumbing or Sewage Violation Since 2024
Records Show 1 in 10 King County Food Vendors Had a Plumbing or Sewage Violation Since 2024

King County Public Health inspected food businesses 71,580 times between January 2024 and September 2026, and closed 27 of them. For restaurant plumbing the real risk is not the citation - it is the backup that stops service, and the closure that follows.

What Is a Sump Pump Used For?
What Is a Sump Pump Used For?

What Is a Sump Pump Used For? A Practical Guide for Washington Homeowners What is a sump pump used for? It removes excess water collecting beneath or around the lowest part of a home before that water spreads across a basement floor or soaks a crawl space. In homes dealing with heavy rain, saturated soil, […]

Tacoma Grease Trap and FOG Compliance Laws
Tacoma Grease Trap and FOG Compliance Laws

Tacoma Grease Trap and FOG Compliance Laws: How Restaurant Owners Can Stay Compliant Running a restaurant in Tacoma means managing more than great food and customer service. Food service establishments must also comply with local Fats, Oils, and Grease (FOG) regulations designed to protect the city’s wastewater system. Failing to maintain your grease interceptor can […]

Contact us


(253) 364-7416
BOOK AN APPOINTMENT
Call (253) 364-7416